Compatible logical node classes and data classes |
LN: Logical node zero Name: LLN0 |
Ln Class: |
LLN0 |
Logical node zero |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
LocKey |
Local operation for complete logical device |
||
LocSta |
Switching authority at station level |
||
Loc |
Local Control Behavior |
||
OpTmh |
Operation time |
||
Controls |
|||
Diag |
Run Diagnostics |
||
LEDRs |
LED reset |
||
Settings |
|||
MltLev |
Select mode of authority for local control |
LN: Neutral current regulator Name: ANCR |
Ln Class: |
ANCR |
Neutral current regulator |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
LocKey |
Local or remote key |
||
LocSta |
Remote Control Blocked |
||
Loc |
Local Control Behavior |
||
OpCntRs |
Resetable operation counter |
||
Controls |
|||
TapChg |
Change Tap Position (stop, higher, lower) |
||
RCol |
Raise Plunge Coil Position |
||
LCol |
Lower Plunge Coil Position |
||
Status Information |
|||
Auto |
Automatic operation |
LN: Reactive power control Name: ARCO |
Ln Class: |
ARCO |
Reactive power control |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
LocKey |
Local or remote key |
||
LocSta |
Remote Control Blocked |
||
Loc |
Local Control Behavior |
||
OpCntRs |
Resetable operation counter |
||
Controls |
|||
TapChg |
Change Tap Position (stop, higher, lower) |
||
Status Information |
|||
Auto |
Automatic operation |
||
VOvSt |
Voltage override status |
||
NeutAlm |
Neutral alarm is present |
||
DschBlk |
Bank switch close blocked due to discharge |
LN: Automatic tap changer controller Name: ATCC |
Ln Class: |
ATCC |
Automatic tap changer controller |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
LocKey |
Local or remote key |
||
LocSta |
Remote Control Blocked |
||
Loc |
Local Control Behavior |
||
OpCntRs |
Resetable operation counter |
||
Controls |
|||
TapChg |
Change Tap Position (stop, higher, lower) |
||
TapPos |
Tap position |
||
BndCtrChg |
Band centre change (raise, lower), no status |
||
ParOp |
Parallel/Independent operation |
||
LTCBlk |
Block (Inhibit) Automatic Control of LTC |
||
LTCDragRs |
Reset LTC Drag Hands |
||
VRed1 |
Voltage reduction step 1 |
||
Measured Values |
|||
CtlV |
Control Voltage |
||
LodA |
Load Current (total transformer secondary current) |
||
CircA |
Circulating Current |
||
PhAng |
Phase Angle of LodA relative to CtlV at 1.0 power factor, FPF |
||
Metered Values |
|||
HiCtlV |
Highest Control Voltage |
||
LoCtlV |
Lowest Control Voltage |
||
HiDmdA |
High current demand (Load Current Demand) |
||
Status Information |
|||
Auto |
Automatic/Manual operation |
||
HiTapPos |
High tap position |
||
LoTapPos |
Low tap position |
||
TapOpR |
Change tap position raise |
||
TapOpLo |
Change tap position lower |
||
TapOpStop |
Change tap position stop |
||
Settings |
|||
BndCtr |
Band center voltage (FPF presumed) |
||
BndWid |
Band width voltage (as voltage or percent of nominal voltage (FPF presumed) |
||
CtlDlTmms |
Control intentional time delay (FPF presumed) |
||
LDCR |
Line drop voltage due to line resistance component |
||
LDCX |
Line drop voltage due to line reactance component |
||
BlkLV |
Control voltage below which auto Lower commands blocked |
||
BlkRV |
Control voltage above which auto Raise commands blocked |
||
BlkVLo |
Control voltage below which auto Raise commands are blocked. |
||
BlkVHi |
Control voltage above which auto Lower commands are blocked. |
||
RnbkRV |
Runback Raise Voltage |
||
LimLodA |
Limit Load Current (LTC Block Load Current) |
||
LDC |
Line Drop Compensation is R&X or Z model |
||
TmDlChr |
Time delay linear or inverse characteristic |
||
LDCZ |
Line impedance for line drop compensation |
||
VRedVal |
Reduction of band centre (percent) when voltage reduction step is active |
||
TapBlkR |
Tap position of Load Tap Changer where automatic Raise commands are blocked |
||
TapBlkL |
Tap position of Load Tap Changer where automatic Lower commands are blocked |
LN: Voltage control Name: AVCO |
Ln Class: |
AVCO |
Voltage control |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
LocKey |
Local or remote key |
||
LocSta |
Remote Control Blocked |
||
Loc |
Local Control Behavior |
||
OpCntRs |
Resetable operation counter |
||
Controls |
|||
TapChg |
Change Tap Position (stop, higher, lower) |
||
Status Information |
|||
Auto |
Automatic/Manual operation |
||
BlkEF |
Blocked by earth fault |
||
BlkAOv |
Blocked by current limit overflow |
||
BlkVOv |
Blocked by Voltage limit overflow |
||
Settings |
|||
LimAOv |
Current limit for overflow blocking |
||
LimVOv |
Voltage limit for overflow blocking |
LN: Alarm handling Name: CALH |
Ln Class: |
CALH |
Alarm handling |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
GrAlm |
Group alarm |
||
GrWrn |
Group warning |
||
GrInd |
Group Indication |
||
AlmLstOv |
Alarm list overflow |
LN: Cooling group control Name: CCGR |
Ln Class: |
CCGR |
Cooling group control |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
||
Measured Values |
|||
EnvTmp |
Temperature of environment |
||
OilTmpIn |
Oil temperature cooler in |
||
OilTmpOut |
Oil temperature cooler out |
||
OilMotA |
Oil circulation motor drive current |
||
FanFlw |
Air flow in fan |
||
CETmpIn |
Temperature of secundary cooling medium in |
||
CETmpOut |
Temperature of secundary cooling medium out |
||
CEPres |
Pressure of secundary cooling medium |
||
CEFlw |
Flow of secundary cooling medium |
||
FanA |
Motor drive current fan |
||
Controls |
|||
CGRBlk |
Control of automatic / manual operation |
||
CECtl |
Control of complete cooling group (pumps and fans) |
||
PmpCtlGen |
Control of all pumps |
||
PmpCtl |
Control of a single pump |
||
FanCtlGen |
Control of all fans |
||
FanCtl |
Control of a single fan |
||
Status Information |
|||
Auto |
Automatic or manual |
||
FanOvCur |
Fan overcurrent trip |
||
PmpOvCur |
Pump overcurrent trip |
||
PmpAlm |
Loss of pump |
||
Settings |
|||
OilTmpSet |
Set point for oil temperature |
LN: Interlocking Name: CILO |
Ln Class: |
CILO |
Interlocking |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
EnaOpn |
Enable Open |
||
EnaCls |
Enable Close |
LN: Point-on-wave switching Name: CPOW |
Ln Class: |
CPOW |
Point-on-wave switching |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Controls |
|||
Pos |
Switch, general |
||
PosA |
Switch L1 |
||
PosB |
Switch L2 |
||
PosC |
Switch L3 |
||
Status Information |
|||
TmExc |
Maximum allowed time exceeded |
||
StrPOW |
CPOW started |
||
OpOpn |
Open switch |
||
OpCls |
Close switch |
||
Settings |
|||
MaxDlTmms |
Maximum allowed delay time |
LN: Switch controller Name: CSWI |
Ln Class: |
CSWI |
Switch controller |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
LocKey |
Local or remote key |
||
LocSta |
Remote Control Blocked |
||
Loc |
Local Control Behavior |
||
OpCntRs |
Resetable operation counter |
||
Controls |
|||
Pos |
Switch, general |
||
PosA |
Switch L1 |
||
PosB |
Switch L2 |
||
PosC |
Switch L3 |
||
Status Information |
|||
OpOpn |
Operation “Open Switch” |
||
SelOpn |
Selection “Open Switch” |
||
OpCls |
Operation “Close Switch” |
||
SelCls |
Selection “Close Switch” |
LN: Synchronizer controller Name: CSYN |
Ln Class: |
CSYN |
Synchronizer controller |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
LocKey |
Local or remote key |
||
LocSta |
Remote Control Blocked |
||
Loc |
Local Control Behavior |
||
OpCntRs |
Resetable operation counter |
||
Controls |
|||
StrSyn |
Start synchronising process |
||
StopSyn |
Stop synchronising process |
||
RelDeaBus |
Releasing Dead Bus / Dead Line function |
||
BlkSyn |
Enable writing parameters to synchronizer |
||
RsSyn |
Reset synchroniser (in error condition) |
||
Status Information |
|||
Cmd |
Command |
||
RV |
Raise Voltage |
||
LV |
Lower Voltage |
||
RHz |
Raise frequency (increase speed) |
||
LHz |
Lower frequency (lower speed) |
||
VInd |
Voltage Difference Indicator |
||
AngInd |
Angle Difference Indicator |
||
HzInd |
Frequency Difference Indicator |
||
SynPrg |
Synchronising in progress |
||
SynFlt |
Synchroniser in error status |
||
SynRdy |
Synchroniser ready to synchronise |
||
SynSetMod |
Synchroniser in setting mode (blocked) |
||
Measured Values |
|||
DifVClc |
Calculated Difference in Voltage (amplitude value) |
||
DifHzClc |
Calculated Difference in Frequency |
||
DifHzClcHi |
Calculated Difference in Frequency (high resolution) |
||
DifAngClc |
Calculated Difference of Phase Angle |
||
V1Clc |
Amplitude value U1 |
||
V2Clc |
Amplitude value U2 |
||
Hz1Clc |
Frequency f1 |
||
Hz2Clc |
Frequency f2 |
||
AccClc |
Acceleration |
||
Settings |
|||
VNomV |
Nominal secondary voltage |
||
HzNom |
Nominal frequency |
||
VAdpFact |
Adaptation factor U1/U2 |
||
AdpAngDeg |
Adaptation angle (e.g. setting group compens.) |
||
BkrTmms |
Closing Time of breaker |
||
PlsTmms |
Close Pulse Time |
||
DlTms |
Supervision time for paralleling |
||
MltCmd |
Multiple Command generation |
||
DifVNg |
Difference Voltage (amplitude value) negative |
||
DifVPs |
Difference Voltage (amplitude value) positive |
||
DifHzNg |
Difference Frequency negative |
||
DifHzPs |
Difference Frequency positive |
||
DifAngNg |
Difference Phase Angle negative |
||
DifAngPs |
Difference Phase Angle positive |
||
MinVSyn |
Minimum voltage for live synchronisation |
||
MaxVSyn |
Maximum voltage for live synchronisation |
||
DetSyn |
Detection of synchronism |
||
LivDeaMod |
Live Dead Mode |
||
DeaLinVal |
Dead Line Value |
||
LivLinVal |
Live Line Value |
||
DeaBusVal |
Dead Bus Value |
||
LivBusVal |
Live Bus Value |
||
VAdj |
Voltage matcher ON / OFF |
||
VChr |
Voltage adjustment characteristic |
||
VInvTms |
Voltage adjustment pulse interval |
||
MinVTms |
Minimum voltage adjustment pulse time |
||
MaxVTms |
Maximum voltage adjustment pulse time |
||
HzAdj |
Frequency matcher ON / OFF |
||
HzChr |
Frequency adjustment characteristic |
||
HzInvTms |
Frequency adjustment pulse interval |
||
MinHzTms |
Minimum frequency adjustment pulse time |
||
MaxHzTms |
Maximum frequency adjustment pulse time |
||
HzTgtVal |
Frequency matcher target value |
||
KckPls |
Kicker pulse ON / OFF |
||
TmTot |
Total time of synchronising process |
LN: Counter Name: FCNT |
Ln Class: |
FCNT |
Counter Name |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Up |
Last count direction upward |
||
Dn |
Last count direction downward |
||
Metered Values |
|||
OpCntRs |
Counter |
LN: Curve shape description Name: FCSD |
Ln Class: |
FCSD |
Curve shape description |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Measured Values |
|||
Out |
Output |
||
Settings |
|||
Crv |
Curve shape |
LN: Generic Filter Name: FFIL |
Ln Class: |
FFIL |
Generic Filter |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Measured Values |
|||
Out |
Output |
||
ErrTerm |
Control loop termination error value |
||
Settings |
|||
FilTyp |
Filter type: | Low pass | High pass | Bandpass | Bandstop (notch) |
||
Kp |
Proportional Gain |
||
Kld |
K lead |
||
Klg |
K lag |
||
T1ms |
Time 1 [ms] |
||
T1ldms |
Time 1 (lead) [ms] |
||
T2ms |
Time 2 [ms] |
||
T2ldms |
Time 2 (lead) [ms] |
||
T3ms |
Time 3 [ms] |
LN: Control function output limitation Name: FLIM |
Ln Class: |
FLIM |
Control function output limitation |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
HiLim |
High limit reached (input signal equal to or above limit) |
||
LoLim |
Low limit reached (input signal equal to or below limit) |
||
Measured Values |
|||
Out |
Output signal |
||
Settings |
|||
HiLimSpt |
High limit setpoint |
||
LoLimSpt |
Minimum limit setpoint |
LN: PID regulator Name: FPID |
Ln Class: |
FPID |
PID regulator |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Measured Values |
|||
Out |
PID output |
||
PAct |
Proportional action |
||
IAct |
Integral action |
||
DAct |
Derivative action |
||
PropOut |
P output |
||
IntgOut |
I output |
||
DerOut |
D output |
||
ErrTerm |
Control loop termination error value |
||
Settings |
|||
PidAlg |
P|I|D|PI|PD|ID|PID| |
||
Kp |
Proportional gain |
||
Ki |
Integral Gain |
||
IntgTmms |
Integral time (ms) |
||
Kd |
Derivative gain |
||
DerTmms |
Derivative time (ms) |
||
DerFilTmms |
Derivative time filter (ms) |
||
Bias |
Bias added to process variable |
LN: Ramp function Name: FRMP |
Ln Class: |
FRMP |
Ramp function |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Measured Values |
|||
Out |
Ramp Output |
||
Status Information |
|||
AdjSt |
State of adjustment process |
||
ErrTerm |
Control loop termination error value |
||
Settings |
|||
RmpUp |
Ramping rate on a upward trend |
||
RmpDn |
Ramping rate on a downward trend |
||
StepPs |
Step size when turning from negative to positive direction |
||
StepNg |
Step size when turning from positive to negative direction |
LN: Set-point control function Name: FSPT |
Ln Class: |
FSPT |
Set-point control function |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
Loc |
LocalControl Behavior |
||
Controls |
|||
SptChg |
Setpoint change (raise, lower) |
||
SptVal |
Setpoint |
||
Measured Values |
|||
SptMem |
Setpoint in memory |
||
ErrTerm |
Control loop termination error value |
||
Out |
Output |
||
Status Information |
|||
Auto |
Automatic operation |
||
SptDvAlm |
Deviation alarm |
||
SptUp |
Setpoint going up (raising) |
||
SptDn |
Setpoint going up (Lowering) |
||
SptDir |
Setpoint direction |
||
SptEndSt |
End status of set-point control |
||
AdjSt |
Adjustment Status |
||
Settings |
|||
MaxRst |
Maximum restriction |
||
MinRst |
Minimum restriction |
||
DvAlm |
Deviation Alarm |
||
DeaB |
Deadband |
LN: Action at over threshold Name: FXOT |
Ln Class: |
FXOT |
Action at over threshold |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Op |
Level of action reached |
||
Settings |
|||
StrVal |
Start level set-point |
||
OpDlTmms |
Operate delay time [ms] |
||
StrCrv |
Start level curve |
||
RsDlTmms |
Reset operate delay time [ms] |
LN: Action at under threshold Name: FXUT |
Ln Class: |
FXUT |
Action at under threshold |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Op |
Level of action reached |
||
Settings |
|||
StrVal |
Start level set-point |
||
OpDlTmms |
Operate delay time [ms] |
||
StrCrv |
Start level curve |
||
RsDlTmms |
Reset operate delay time [ms] |
LN: Generic automatic process control Name: GAPC |
Ln Class: |
GAPC |
Generic automatic process control |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
LocKey |
Local or remote key |
||
LocSta |
Remote Control Blocked |
||
Loc |
Local Control Behavior |
||
OpCntRs |
Resetable operation counter |
||
Controls |
|||
SPCSO1 |
Single point controllable status output |
||
DPCSO1 |
Double point controllable status output |
||
ISCSO1 |
Integer status controllable status output |
||
Status Information |
|||
Auto1 |
Automatic operation |
||
Str1 |
Start |
||
Op1 |
Operate |
||
Alm1 |
Generic single alarm |
||
Wrn1 |
Generic single warning |
||
Ind1 |
Generic single indication |
||
Settings |
|||
StrVal1 |
Start Value |
LN: Generic process I/O Name: GGIO |
Ln Class: |
GGIO |
Generic process I/O |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health (external sensor) |
||
EEName |
External equipment name plate |
||
LocKey |
Local or remote key |
||
LocSta |
Remote Control Blocked |
||
Loc |
Local Control Behavior |
||
OpCntRs |
Resetable operation counterr |
||
Measured Values |
|||
AnIn1 |
Analogue input |
||
AnOut1 |
Controllable analogue output |
||
Controls |
|||
SPCSO1 |
Single point controllable status output |
||
DPCSO1 |
Double point controllable status output |
||
ISCSO1 |
Integer status controllable status output |
||
Metered Values |
|||
CntRs1 |
Counter, resetablen |
||
Status Information |
|||
IntIn1 |
Integer status input |
||
Alm1 |
General single alarm |
||
Wrn1 |
General single warning |
||
Ind1 |
General indication (binary input) |
LN: Generic log Name: GLOG |
Ln Class: |
GLOG |
Generic log |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Controls |
|||
OpCntRs |
Counts the events logged (resettable) |
||
LogTrg |
TriggerLogging by operator |
||
Settings |
|||
LogRef |
Reference to Log |
||
TrgRef1 |
Trigger reference shows the receiving trigger signal |
||
InRef1 |
Reference to data objects / data attributes to include in LOG acc. |
LN: Generic security application Name: GSAL |
Ln Class: |
GSAL |
Generic security application |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
OpCntRs |
Resetable operation counter. NOTE – An operation in the context of this logical node is a security violation |
||
Status Information |
|||
AuthFail |
Authorisation failures |
||
AcsCtlFail |
Access control failures detected |
||
SvcViol |
Service privilege violations |
||
Ina |
Inactive associations |
||
NumCntRs |
Number of counter resets |
LN: Archiving Name: IARC |
Ln Class: |
IARC |
Archiving |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
MemOv |
Memory Overflow |
||
MemUsed |
Memory used in % |
||
NumRcd |
Actual number of records |
||
InTrg |
Reference to trigger |
||
InLog |
Reference to Data Objects |
||
Settings |
|||
MaxNumRcd |
Maximum number of records O |
||
OpMod |
Operation mode (Saturation, Overwrite) |
||
MemFull |
Memory full level |
LN: Human machine interface Name: IHMI |
Ln Class: |
IHMI |
Human machine interface |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
LocKey |
Local or remote key |
||
LocSta |
Remote Control Blocked |
||
Loc |
Local Control Behavior |
LN: Safety alarm function Name: ISAF |
Ln Class: |
ISAF |
Safety alarm function |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Alm |
Safety alarm (True=On, False=Off) |
||
Controls |
|||
AlmReset |
Alarm signal reset |
||
OpCntRs |
Resetable operation counter |
LN: Telecontrol interface Name: ITCI |
Ln Class: |
ITCI |
Telecontrol interface |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
LocKey |
Local or remote key |
||
LocSta |
Remote Control Blocked |
||
Loc |
Local Control Behavior |
LN: Fan Name: KFAN |
Ln Class: |
KFAN |
Fan |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment nameplate |
||
OpTmh |
Operation time |
||
Settings |
|||
DMinOpTmm |
Minimum operation time in minutes |
||
DMaxOpTmm |
Maximum operation time in minutes |
||
Measured Values |
|||
Spd |
Rotational speed of the fan |
||
Controls |
|||
Oper |
Operate fan |
||
SpdSpt |
Speed set-point (in case of speed regulated motor) |
LN: Filter Name: KFIL |
Ln Class: |
KFIL |
Filter |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment nameplate |
||
OpTmh |
Operation time |
||
Status Information |
|||
ACAlm |
AC supply failure (fuse or other problem) |
||
MotPro |
Motor protection tripped |
||
Flush |
Filter flushing |
||
FlushCnt |
Filter flushing counter (reset-able) |
||
FilAlm |
Filter alarm |
||
Measured Values |
|||
DifPresHi |
Differential pressure over the filter |
||
Controls |
|||
Oper |
Operate filter |
||
Settings |
|||
AlmLevSpt |
Alarm level set-point |
LN: Pump Name: KPMP |
Ln Class: |
KPMP |
Pump |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment nameplate |
||
OpTmh |
Operation time |
||
Settings |
|||
MinOpTmm |
Minimum operation time in minutes |
||
MaxOpTmm |
Maximum operation time in minutes |
||
Measured Values |
|||
Spd |
Rotational speed of the pump |
||
Controls |
|||
Oper |
Operate pump |
||
SpdSpt |
Speed set-point (in case of speed regulated motor) |
LN: Tank Name: KTNK |
Ln Class: |
KTNK |
Tank |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment nameplate |
||
LocKey |
Local-remote key |
||
Settings |
|||
VlmCap |
Total volume capacity |
||
TnkTyp |
Type of data representing the tank fill status (pressure only, level only, both pressure and level) |
||
Measured Values |
|||
LevPct |
Level in the tank (as percentage of full tank level) |
||
Vlm |
Volume of media in tank |
LN: Valve control Name: KVLV |
Ln Class: |
KVLV |
Valve |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment nameplate |
||
OpCnt |
Operation counter |
||
LocKey |
Local-remote key |
||
Status Information |
|||
ClsPos |
Closed end position reached (valve cannot move further) |
||
OpnPos |
Open end position reached (valve cannot move further) |
||
Mvm |
Valve is moving |
||
Stuck |
Valve is blocked (cannot move from present position) |
||
Settings |
|||
OpnLim |
Opening limit of valve position (temporary restriction) |
||
ClsLim |
Closing limit of valve position (temporary restriction) |
||
Incr |
Increment of position change for open / close commands |
||
Measured Values |
|||
PosVlv |
Valve position |
||
Flw |
Calculated liquid flow through the valve [m3 / s] |
||
Controls |
|||
PosSpt |
Valve position set-point |
||
Pos |
Valve to full open or closed position |
||
PosChg |
Change valve position (stop, raise, lower) |
||
PosChgIncr |
Incremental change of position |
||
BlkOpn |
Block opening of the valve |
||
BlkCls |
Block closing of the valve |
LN: Advanced Measurement unit Name: MADV |
Ln Class: |
MADV |
Advanced Measurement unit |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Measured Values |
|||
TotVAa |
Arithmetic Total Apparent Power (va) |
||
TotVAv |
Vector Total Apparent Power (va) |
||
TotVAaFund |
Fundamental Arithmetic Total Apparent Power (va) |
||
TotVAvFund |
Fundamental Vector Total Apparent Power (va) |
||
TPF |
True Power Factor (pu) |
||
TPFworst |
Worst Phase True Power Factor (pu) |
||
AvgTPF |
Average True Power Factor (pu) |
||
TotPFa |
Arithmetic Total Power Factor (pu) |
||
TotPFv |
Vector Total Power Factor (pu) |
||
DspPF |
Displacement Power Factor (pu), fundamental power factor |
||
DspPFworst |
Worst Phase Displacement Power Factor (pu) |
||
AvDspPF |
Average Displacement Power Factor (pu) |
||
TotDspPFa |
Arithmetic Total Displacement Power Factor (pu) |
||
TotDspPFv |
Vector Total Displacement Power Factor (pu) |
||
Ires |
Residual Current Ia + Ib + Ic (amps) |
||
Inet |
Net Current Ia + Ib + Ic + In (amps) |
||
NsN |
non-active power (vars) |
||
NsSn |
Non-fundamental apparent power |
||
NsSh |
harmonic apparent power |
||
NsDpi |
current distortion power |
||
NsDpv |
voltage distortion power |
||
NsDph |
harmonic distortion power |
||
NsSnS1 |
Sn / S1 ratio – harmonic pollution |
||
NsIeh |
3 phase effective harmonic current |
||
NsVeh |
3 phase effective harmonic voltage |
||
NsSeh |
3 phase effective harmonic apparent power |
||
NsDpei |
3 phase effective current distortion power |
||
NsDpev |
3 phase effective voltage distortion power |
||
NsDpeh |
3 phase effective harmonic distortion power |
||
NsSen |
3 phase effective non-fundamental apparent power |
||
NsSenSe1 |
Sen / Se1 ratio – harmonic pollution |
||
NsS1 |
fundamental apparent power (va) |
||
NsP1 |
fundamental real power (watts) |
||
NsSn |
non-active apparent power (vars) |
||
NsIe |
3 phase effective current (amps) |
||
NsVe |
3 phase effective voltage (volts) |
||
NsSe |
3 phase effective apparent power (va) |
||
NsIe1 |
3 phase effective fundamental current (amps) |
||
NsVe1 |
3 phase effective fundamental voltage (volts) |
||
NsSe1 |
3 phase effective fundamental apparent power (va) |
||
NsTotN |
3 phase total non-active power (vars) |
||
NsPFe |
3 phase effective power factor (pu) |
||
NsS1p |
positive sequence fundamental apparent power (va) |
||
NsS1u |
fundamental unbalanced apparent power (va) |
||
NsP1p |
positive sequence fundamental apparent power (va) |
||
NsQ1p |
positive sequence fundamental reactive power (var) |
||
NsPF1p |
positive sequence fundamental power factor (pu) |
||
NsS1uS1p |
ratio of fundamental unbalance to apparent power (pu) |
LN: Differential measurements Name: MDIF |
Ln Class: |
MDIF |
Differential measurements |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Measured Values |
|||
OpARem |
Operate Current (phasor) of the local current measurement |
||
Amp |
Operate Current (Sampled value) of the local current measurement |
||
Status Information |
|||
SynSt |
Synchronization status (TRUE: synchronized, FALSE: not synchronized) |
LN: Environmental information Name : MENV |
Ln Class: |
MENV |
Environmental information |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Measured Values |
|||
CO2 |
CO2 emissions |
||
CO |
CO emissions |
||
NOx |
NOx emissions |
||
SOx |
SOx emissions |
||
Dust |
Dust particles suspended in air |
||
Snd |
Sound pressure level |
||
O2 |
Oxygen in combustion gases |
||
O3 |
Ozone in air |
||
Settings |
|||
CTrade |
Involved in carbon trading |
||
CCredit |
Carbon production credit value |
||
GreenTag |
Green tag information |
LN: Flicker Measurement unit Name Name: MFLK |
Ln Class: |
MFLK |
Flicker Measurement unit |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Measured Values |
|||
PPPst |
Pst of last complete interval for phase to phase measurements |
||
PhPst |
Pst of last complete interval for phase to ground measurements |
||
PPPlt |
Plt of last complete interval for phase to phase measurements |
||
PhPlt |
Plt of last complete interval for phase to ground measurements |
||
PPPiMax |
Output 5 – Instantaneous peak P value for phase to phase measurements |
||
PhPiMax |
Output 5 – Instantaneous peak P value for phase to ground measurements |
||
PPPiLPF |
Output 4 – 1 minute average of Output 5 for phase to phase measurements |
||
PhPiLPF |
Output 4 – 1 minute average of Output 5 for phase to ground measurements |
||
PPPiRoot |
Output 3 – Square root of Output 5 for phase to phase measurements |
||
PhPiRoot |
Output 3 – Square root of Output 5 for phase to ground measurements! |
||
PPPcbLs |
Classifier bins of last complete short interval for phase to phase(AB, BC, CA) |
||
PhPcbLs |
Classifier bins of last complete short interval for phase to ground (A, B, C) |
||
PPPcbLl |
Classifier bins of last complete long interval for phase to phase (AB, BC, CA) |
||
PhPcbLl |
Classifier bins of last complete long interval for phase to ground (A, B, C) |
||
PPPdmWave |
Real time demodulated waveform for phase to phase (AB, BC, CA) |
||
PhPdmWave |
Real time demodulated waveform for phase tp ground (A, B, C) |
||
PPPdmSpec |
Real time demodulated waveform spectra for phase to phase (AB, BC, CA) |
||
PhPdmSpec |
Real time demodulated waveform spectra for phase to ground (A, B, C)! |
LN: Harmonics or interharmonics Name: MHAI |
Ln Class: |
MHAI |
Harmonics or interharmonics |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Measured Values |
|||
Hz |
Basic frequency |
||
HA |
Sequence of Harmonics or Interharmonics current |
||
HPhV |
Sequence of Harmonics or Interharominics phase to ground voltages |
||
HPPV |
Sequence of Harmonics or Interharmonics phase to phase voltages |
||
HW |
Sequence of Harmonics or Interharmonics active power |
||
HVAr |
Sequence of Harmonics or Interharmonics reactive power |
||
HVA |
Sequence of Harmonics or Interharmonics apparent power |
||
HRmsA |
Current RMS Harmonic or Interharmonics (un-normalized Total harmonic disortion, Thd) |
||
HRmsPhV |
Voltage RMS Harmonic or Interharmonics (un-normalized Thd) for phase to ground |
||
HRmsPPV |
Voltage RMS Harmonic or Interharmonics (un-normalized Thd) for phase to phase |
||
HTuW |
Total phase Harmonic or Interharmonics active power (no fundamental) unsigned sum |
||
HTsW |
Total phase Harmonic or Interharmonic active power (no fundamental) signed sum |
||
HATm |
Current Time product |
||
HKf |
K Factor |
||
HTdf |
Transformer derating factor |
||
ThdA |
Current Total Harmonic or Interharmonic Distortion (different methods) |
||
ThdOddA |
Current Total Harmonic or Interharmonic Distortion (different methods – odd components) |
||
ThdEvnA |
Current Total Harmonic or Interharmonic Distortion (different methods – even components) |
||
TddA |
Current Total Demand Distortion per IEEE 519 |
||
TddOddA |
Current Total Demand Distortion per IEEE 519 (odd components) |
||
TddEvnA |
Current Total Demand Distortion per IEEE 519 (even components) |
||
ThdPhV |
Voltage Total Harmonic or Interharmonic Distortion (different methods) for phase to ground |
||
ThdOddPhV |
Voltage Total Harmonic or Interharmonic Distortion (different methods) for phase to ground (odd components) |
||
ThdEvnPhV |
Voltage Total Harmonic or Interharmonic Distortion (different methods) for phase to ground (even components) |
||
ThdPPV |
Voltage Total Harmonic or Interharmonic Distortion (different methods) for phase to phase |
||
ThdOddPPV |
Voltage Total Harmonic or Interharmonic Distortion (different methods) for phase to phase (odd components) |
||
ThdEvnPPV |
Voltage Total Harmonic or Interharmonic Distortion (different methods) for phase to phase (even components) |
||
HCfPhV |
Voltage crest factors (peak waveform value/sqrt(2)/fundamental) for phase to ground |
||
HCfPPV |
Voltage crest factors (peak waveform value/sqrt(2)/fundamental) for phase to phase |
||
HCfA |
Current crest factors (peak waveform value/sqrt(2)/fundamental) |
||
HTif |
Voltage Telephone Influence Factor |
||
Settings |
|||
HzSet |
Basic frequency |
||
EvTmms |
Evaluation time (time window) determines the lowest frequency |
||
NumCyc |
Number of cycles of the basic frequency |
||
ThdAVal |
ThdA alarm Setting – value entered in % |
||
ThdVVal |
ThdPhV / ThdPPV alarm Setting – value entered in % |
||
ThdATmms |
ThdA alarm time delay in ms |
||
ThdVTmms |
ThdPhV / ThdPPV alarm time delay in ms |
||
NomA |
Normalising demand current used in IEEE 519 TDD calculation |
LN: Non phase related harmonics or interharmonics Name: MHAN |
Ln Class: |
MHAN |
Non phase related harmonics or interharmonics |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Measured Values |
|||
Hz |
Basic frequency |
||
HaAmp |
Sequence of Harmonics or Interharmonics for current |
||
HaVol |
Sequence of Harmonics or Interharmonics for voltages |
||
HaWatt |
Sequence of Harmonics or Interharmonics for active power |
||
HaVolAmpr |
Sequence of Harmonics or Interharmonics for reactive power |
||
HaVolAmp |
Sequence of Harmonics or Interharmonics for apparent power |
||
HaRmsAmp |
Current RMS Harmonic or Interharmonic (un-normalized Thd) |
||
HaRmsVol |
Voltage RMS Harmonic or Interharmonic (un-normalized Thd) |
||
HaTuWatt |
Total Harmonic or Interharmonic active power (no fundamental) unsigned sum |
||
HaTsWatt |
Total Harmonic or Interharmonic active power (no fundamental) signed sum |
||
HaAmpTm |
Current Time product |
||
HaKFact |
K Factor |
||
HaTdFact |
Transformer derating factor |
||
ThdAmp |
Current Total Harmonic or Interharmonic Distortion (different methods) |
||
ThdOddAmp |
Current Total Harmonic or Interharmonic Distortion (different methods – odd components) |
||
ThdEvnAmp |
Current Total Harmonic or Interharmonic Distortion (different methods – even components) |
||
TddAmp |
Current Total Demand Distortion per IEEE 519 |
||
TddOddAmp |
Current Total Demand Distortion per IEEE 519 (odd components) |
||
TddEvnAmp |
Current Total Demand Distortion per IEEE 519 (even components) |
||
ThdVol |
Voltage Total Harmonic or Interharmonic Distortion (different methods) |
||
ThdOddVol |
Voltage Total Harmonic or Interharmonic Distortion (different methods – odd components) |
||
ThdEvnVol |
Voltage Total Harmonic or Interharmonic Distortion (different methods even components) |
||
HaCfAmp |
Current crest factors (peak waveform value/sqrt(2)/fundamental) |
||
HaCfVol |
Voltage crest factors (peak waveform value/sqrt(2)/fundamental) |
||
HaTiFact |
Voltage Telephone Influence Factor |
||
Settings |
|||
HzSet |
Basic frequency |
||
EvTmms |
Evaluation time (time window) determines the lowest frequency |
||
NumCyc |
Number of cycles of the basic frequency |
||
ThdAVal |
ThdA alarm Setting – value entered in % |
||
ThdVVal |
ThdV alarm Setting – value entered in % |
||
ThdATmms |
ThdA alarm time delay in ms |
||
ThdVTmms |
ThdV alarm time delay in ms |
||
NomA |
Normalising demand current used in IEEE 519 TDD calculation |
LN: Hydrological information Name: MHYD |
Ln Class: |
MHYD |
Hydrological information |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Measured Values |
|||
Lev |
Water level [m] |
||
Flw |
River, Stream, Canal Volumetric Flow [m3/s] |
||
SpdSrfc |
Surface speed of water flow [m/s] |
||
Tmp |
Temperature of water [° C] |
||
Cndct |
Electrical conductivity of water [S/cm2] |
||
HydPH |
pH of water (0-14) |
||
Slnt |
Saline content of water [g/l] |
||
Metered Values |
|||
FishCnt |
Fish counter reading |
LN: DC measurement Name: MMDC |
Ln Class: |
MMDC |
DC measurement |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Measured Values |
|||
Watt |
Power |
||
Amp |
Current (DC current) |
||
Vol |
Voltage (DC voltage) between poles |
||
VolPsGnd |
Voltage between positive pole and earth |
||
VolNgGnd |
Voltage between negative pole and earth |
||
Ris |
Resistance in DC circuit |
||
RisPsGnd |
Resistance between positive pole and earth |
||
RisNgGnd |
Resistance between negative pole and earth |
LN: Meteorological information Name: MMET |
Ln Class: |
MMET |
Meteorological information |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Measured Values |
|||
EnvTmp |
Ambient temperature |
||
WetBlbTmp |
Wet bulb temperature |
||
CloudCvr |
Cloud cover level |
||
EnvHum |
Humidity |
||
DewPt |
Dew point |
||
DifInsol |
Diffuse insolation |
||
DirInsol |
Direct normal insolation |
||
DlDur |
Daylight Duration (time elapsed between sunrise and sunset) |
||
HorInsol |
Total Horizontal Insolation |
||
HorWdDir |
Horizontal Wind direction |
||
HorWdSpd |
Average Horizontal Wind speed |
||
VerWdDir |
Vertical Wind Direction |
||
VerWdSpd |
Average Vertical Wind speed |
||
WdGustSpd |
Max Wind gust speed |
||
EnvPres |
Barometric pressure |
||
RnFll |
Rainfall |
||
SnwDen |
Density of snowfall |
||
SnwTmp |
Temperature of snowfall |
||
SnwCvr |
Snowcover |
||
SnwFll |
Snowfall |
||
SnwEq |
Water equivalent of snowfall |
LN: Metering Name: MMTN |
Ln Class: |
MMTN |
Metering |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Metered Values |
|||
TotVAh |
Net apparent energy since last reset |
||
TotWh |
Net Real energy since last reset |
||
TotVArh |
Net Reactive energy since last reset |
||
SupWh |
Real energy supply (default supply direction: energy flow towards busbar) |
||
SupVArh |
Reactive energy supply (default supply direction: energy flow towards busbar) |
||
DmdWh |
Real energy demand (default demand direction: energy flow from busbar away) |
||
DmdVArh |
Reactive energy demand (default demand direction: energy flow from busbar away) |
LN: Metering Name: MMTR |
Ln Class: |
MMTR |
Metering |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Metered Values |
|||
TotVAh |
Net apparent energy since last reset |
||
TotWh |
Net Real energy since last reset |
||
TotVArh |
Net Reactive energy since last reset |
||
SupWh |
Real energy supply (default supply direction: energy flow towards busbar) |
||
SupVArh |
Reactive energy supply (default supply direction: energy flow towards busbar) |
||
DmdWh |
Real energy demand (default demand direction: energy flow from busbar away) |
||
DmdVArh |
Reactive energy demand (default demand direction: energy flow from busbar away) |
LN: Non phase related Measurement Name: MMXN |
Ln Class: |
MMXN |
Non phase related Measurement |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Measured Values |
|||
Amp |
Current I not allocated to a phase |
||
Vol |
Voltage V not allocated to a phase |
||
Watt |
Power (P) not allocated to a phase |
||
VolAmpr |
Reactive Power (Q) not allocated to a phase |
||
VolAmp |
Apparent Power (S) not allocated to a phase |
||
PwrFact |
Power Factor not allocated to a phase |
||
Imp |
Impedance |
||
Hz |
Frequency |
LN: Measurement Name: MMXU |
Ln Class: |
MMXU |
Measurement |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Measured Values |
|||
TotW |
Total Active Power (Total P) |
||
TotVAr |
Total Reactive Power (Total Q) |
||
TotVA |
Total Apparent Power (Total S) |
||
TotPF |
Average Power factor (Total PF) |
||
Hz |
Frequency |
||
PPV |
Phase to phase voltages (VL1VL2, …) |
||
PZV |
Phase to zero voltage |
||
PhV |
Phase to ground voltages (VL1ER, …) |
||
A |
Phase currents (IL1, IL2, IL3) |
||
W |
Phase active power (P) |
||
VAr |
Phase reactive power (Q) |
||
VA |
Phase apparent power (S) |
||
PF |
Phase power factor |
||
Z |
Phase Impedance |
LN: Sequence and imbalance Name: MSQI |
Ln Class: |
MSQI |
Sequence and imbalance |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Measured Values |
|||
SeqA |
Positive, Negative and Zero Sequence Current |
||
SeqV |
Positive, Negative and Zero Sequence Voltage |
||
DQ0Seq |
DQ0 Sequence |
||
ImbA |
Imbalance current |
||
ImbNgA |
Imbalance negative sequence current |
||
ImbNgV |
Imbalance negative sequence voltage |
||
ImbPPV |
Imbalance phase-phase voltage |
||
ImbV |
Imbalance voltage |
||
ImbZroA |
Imbalance zero sequence current |
||
ImbZroV |
Imbalance zero sequence voltage |
||
MaxImbA |
Maximum imbalance current |
||
MaxImbPPV |
Maximum imbalance phase-phase voltage |
||
MaxImbV |
Maximum imbalance voltage |
LN: Differential Name: PDIF |
Ln Class: |
PDIF |
Differential |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate |
||
TmASt |
Active curve |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Measured Values |
|||
DifAClc |
Differential Current |
||
RstA |
Restraint Current |
||
Settings |
|||
LinCapac |
Line capacitance (for load currents) |
||
LoSet |
Low operate value, percentage of the nominal current |
||
HiSet |
High operate value, percentage of the nominal current |
||
MinOpTmms |
Minimum Operate Time |
||
MaxOpTmms |
Maximum Operate Time |
||
RstMod |
Restraint Mode |
||
RsDlTmms |
Reset Delay Time |
||
TmACrv |
Operating Curve Type |
||
TmAChr33 |
Multiline curve characteristic definition |
LN: Direction comparison Name: PDIR |
Ln Class: |
PDIR |
Direction comparison |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start (appearance of the first related fault direction) |
||
Op |
Operate (decision from all sensors that the surrounded object is faulted) |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
RsDlTmms |
Reset Time Delay |
LN: Distance Name: PDIS |
Ln Class: |
PDIS |
Distance |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
PoRch |
Polar Reach is the diameter of the Mho diagram |
||
PhStr |
Phase Start Value |
||
GndStr |
Ground Start Value |
||
DirMod |
Directional Mode |
||
PctRch |
Percent Reach |
||
Ofs |
Offset |
||
PctOfs |
Percent Offset |
||
RisLod |
Resistive reach for load area |
||
AngLod |
Angle for load area |
||
TmDlMod |
Operate Time Delay Mode |
||
OpDlTmms |
Operate Time Delay |
||
PhDlMod |
Operate Time Delay Multiphase Mode |
||
PhDlTmms |
Operate Time Delay for Multiphase Faults |
||
GndDlMod |
Operate Time Delay for Single Phase Ground Mode |
||
GndDlTmms |
Operate Time Delay for single phase ground faults |
||
X1 |
Positive sequence line (reach) reactance |
||
LinAng |
Line Angle |
||
RisGndRch |
Resistive Ground Reach |
||
RisPhRch |
Resistive Phase Reach |
||
K0Fact |
Residual Compensation Factor K0 |
||
K0FactAng |
Residual Compensation Factor Angle |
||
RsDlTmms |
Reset Time Delay |
LN: Directional overpower Name: PDOP |
Ln Class: |
PDOP |
Directional overpower |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
DirMod |
Directional Mode |
||
StrVal |
Start Value |
||
OpDlTmms |
Operate Delay Time |
||
RsDlTmms |
Reset Delay Time |
LN: Directional underpower Name: PDUP |
Ln Class: |
PDUP |
Directional underpower |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
StrVal |
Start Value |
||
OpDlTmms |
Operate Delay Time |
||
RsDlTmms |
Reset Delay Time |
||
DirMod |
Directional Mode |
LN: Rate of change of frequency Name: PFRC |
Ln Class: |
PFRC |
Rate of change of frequency |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate |
||
BlkV |
Blocked because of voltage |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
StrVal |
Start Value df/dt |
||
BlkVal |
Voltage Block Value |
||
OpDlTmms |
Operate Delay Time |
||
RsDlTmms |
Reset Delay Time |
LN: Harmonic restraint Name: PHAR |
Ln Class: |
PHAR |
Harmonic restraint |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Settings |
|||
Str |
Start (active when restraint is needed) |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Status Information |
|||
HaRst |
Number of harmonic restrained |
||
PhStr |
Start Value |
||
PhStop |
Stop Value |
||
OpDlTmms |
Operate Delay Time |
||
RsDlTmms |
Reset Delay Time |
LN: Ground detector Name: PHIZ |
Ln Class: |
PHIZ |
Ground detector |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
AStr |
Current Start Value |
||
VStr |
Voltage Start Value |
||
HVStr |
Third Harmonic Voltage Start Value |
||
OpDlTmms |
Operate Delay Time |
||
RsDlTmms |
Reset Delay Time |
LN: Instantaneous overcurrent Name: PIOC |
Ln Class: |
PIOC |
Instantaneous overcurrent |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
StrVal |
Start Value |
LN: Motor restart inhibition Name: PMRI |
Ln Class: |
PMRI |
Motor restart inhibition |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Op |
Operate |
||
StrInh |
Restart inhibited |
||
StrInhTmm |
Restart Inhibition Time |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
SetA |
Current setting for motor start-up |
||
SetTms |
Time Setting for motor start-up |
||
MaxNumStr |
Maximum number of starts (also for cold starts) |
||
MaxWrmStr |
Maximum Warm Starts, permissible number of warm starts |
||
MaxStrTmm |
Time period for the maximum number of starts |
||
EqTmm |
Temperature Equalisation Time |
||
InhTmm |
Restart Inhibit Time |
LN: Motor starting time supervision Name: PMSS |
Ln Class: |
PMSS |
Motor starting time supervision |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
SetA |
Current setting for motor start-up |
||
SetTms |
Time Setting for motor start-up |
||
MotStr |
I Motor Startup, (current pickup value of motor starting) |
||
LokRotTms |
Lock Rotor Time, permissible locked rotor time |
LN: Over power factor Name: POPF |
Ln Class: |
POPF |
Over power factor |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate |
||
BlkA |
Blocked below minimum operating current |
||
BlkV |
Blocked below minimum operating voltage |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
StrVal |
Start Value |
||
OpDlTmms |
Operate Delay Time |
||
RsDlTmms |
Reset Delay Time |
||
BlkValA |
Block Value (Minimum operating current) |
||
BlkValV |
Block Value (Minimum operating voltage) |
LN: Phase angle measuring Name: PPAM |
Ln Class: |
PPAM |
Phase angle measuring |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
StrVal |
Start Value |
LN: Rotor protection Name: PRTR |
Ln Class: |
PRTR |
Rotor protection |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate (trips both field CB and generator CB) |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
StrVal |
Start Value |
LN: Protection scheme Name: PSCH |
Ln Class: |
PSCH |
Protection scheme |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
OpCntRs |
Resetable operation counter |
||
TxPrm |
Permissive information to be transmitted to the other side (Teleprotection permissive signal) |
||
TxBlk |
Blocking information to be transmitted to the other side (Teleprotection blocking signal) |
||
TxTr |
Direct trip information to be transmitted to the other side |
||
RxPrm1 |
Activation information RxPrm1 received from the other side(s), for logging purposes (Teleprotection permissive signal received)) |
||
RxBlk1 |
Activation information RxBlk1 received from the other side(s), for logging purposes (Teleprotection blocking signal received) |
||
RxTr1 |
Activation information RxTr1 received from the other side(s), for logging purposes (direct trip signal received) |
||
Op |
Operate |
||
Echo |
TxPrm is being sent as echo signal (in case of weak infeed) |
||
WeiOp |
Indicates operate from weak end infeed function (typically with undervoltage control) |
||
BlkSta |
Teleprotection in blocked state |
||
Settings |
|||
RxSrc1 |
Source for activation information RxPrm or RxBlk, must refer to Data Objects of type ACT |
||
RxSrcTr1 |
Source for activation information RxTr, must refer to Data Objects of type ACT |
||
OpDlTmms |
Operate Delay Time |
||
CrdTmms |
Co-ordination timer for blocking scheme |
||
DurTmms |
Minimum duration of TxPerm in case of operate of PSCH |
||
UnBlkMod |
Unblock function mode for scheme type |
||
UnBlkTmms |
Unblocking time (check application??) |
||
WeiMod |
Mode of weak end infeed function |
||
WeiTmms |
Co-ordination time for weak end infeed function |
LN: Sensitive directional earthfault Name: PSDE |
Ln Class: |
PSDE |
Sensitive directional earthfault |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
Ang |
Angle between voltage (Uo) and current (Io) |
||
GndStr |
Ground Start Value (3 Uo) |
||
GndOp |
Ground Operate Value (3 Io) |
||
StrDlTmms |
Start Delay Time |
||
OpDlTmms |
Operate Delay Time |
||
DirMod |
Directional Mode |
LN: Transient earth fault Name: PTEF |
Ln Class: |
PTEF |
Transient earth fault |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start (Transient earth fault) |
||
Op |
Operate (Transient earth fault) |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
GndStr |
Ground Start Value |
||
DirMod |
Directional Mode |
LN: Tyristor protection Name: PTHF |
Ln Class: |
PTHF |
Tyristor protection |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate (trips both field CB and generator CB) |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
StrVal |
Start Value |
LN: Time overcurrent Name: PTOC |
Ln Class: |
PTOC |
Time overcurrent |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate |
||
TmASt |
Active curve characteristic |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
TmACrv |
Operating Curve Type |
||
TmAChr33 |
Multiline curve characteristic definition |
||
StrVal |
Start Value |
||
TmMult |
Time Dial Multiplier |
||
MinOpTmms |
Minimum Operate Time |
||
MaxOpTmms |
Maximum Operate Time |
||
OpDlTmms |
Operate Delay Time |
||
TypRsCrv |
Type of Reset Curve |
||
RsDlTmms |
Reset Delay Time |
||
DirMod |
Directional Mode |
LN: Overfrequency Name: PTOF |
Ln Class: |
PTOF |
Overfrequency |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate |
||
BlkV |
Blocked because of voltage |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
StrVal |
Start Value (frequency) |
||
BlkVal |
Voltage Block Value |
||
OpDlTmms |
Operate Delay Time |
||
RsDlTmms |
Reset Delay Time |
LN: Overvoltage Name: PTOV |
Ln Class: |
PTOV |
Overvoltage |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate |
||
TmVSt |
Active curve characteristic |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
TmACrv |
Operating Curve Type |
||
TmAChr33 |
Multiline curve characteristic definition |
||
StrVal |
Start Value |
||
TmMult |
Time Dial Multiplier |
||
MinOpTmms |
Minimum Operate Time |
||
MaxOpTmms |
Maximum Operate Time |
||
OpDlTmms |
Operate Delay Time |
||
RsDlTmms |
Reset Delay Time |
LN: Protection trip conditioning Name: PTRC |
Ln Class: |
PTRC |
Protection trip conditioning |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Tr |
Trip |
||
Op |
Operate (combination of subscribed Op from protection functions) |
||
Str |
Start (combination of subscribed Str from protection functions) |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
TrMod |
Trip Mode |
||
TrPlsTmms |
Trip Pulse Time |
LN: Thermal overload Name: PTTR |
Ln Class: |
PTTR |
Thermal overload |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Measured Values |
|||
Amp |
Current for thermal load model |
||
Tmp |
Temperature for thermal load |
||
TmpRl |
Relation between temperature and max. temperature |
||
LodRsvAlm |
Load reserve to alarm |
||
LodRsvTr |
Load reserve to trip |
||
Status Information |
|||
Str |
Start |
||
Op |
Operate |
||
AlmThm |
Thermal Alarm |
||
TmTmpSt |
Active curve characteristic |
||
TmASt |
Active curve characteristic |
||
BlkThm |
Block closing command for circuit breaker because of thermal condition |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
TmTmpCrv |
Characteristic Curve for temperature measurement |
||
TmTmpChr33 |
Multiline curve characteristic definition |
||
TmACrv |
Characteristic Curve for current measurement /Thermal model |
||
TmAChr33 |
Multiline curve characteristic definition |
||
TmpMax |
Maximum allowed temperature |
||
StrVal |
Start Value |
||
OpDlTmms |
Operate Delay Time |
||
MinOpTmms |
Minimum Operate Time |
||
MaxOpTmms |
Maximum Operate Time |
||
RsDlTmms |
Reset Delay Time |
||
ConsTms1 |
Time constant of the thermal model |
||
AlmVal |
Alarm Value |
||
DropoutVal |
Value for blocking closing command |
LN: Undercurrent Name: PTUC |
Ln Class: |
PTUC |
Undercurrent |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate |
||
TmASt |
Active curve characteristic |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
TmACrv |
Operating Curve Type |
||
TmAChr33 |
Multiline curve characteristic definition |
||
StrVal |
Start Value |
||
OpDlTmms |
Operate Delay Time |
||
TmMult |
Time Dial Multiplier |
||
MinOpTmms |
Minimum Operate Time |
||
MaxOpTmms |
Maximum Operate Time |
||
TypRsCrv |
Type of Reset Curve |
||
RsDlTmms |
Reset Delay Time |
||
DirMod |
Directional Mode |
LN: Underfrequency Name: PTUF |
Ln Class: |
PTUF |
Underfrequency |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate |
||
BlkV |
Blocked because of voltage |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
StrVal |
Start Value (frequency) |
||
BlkVal |
Voltage Block Value |
||
OpDlTmms |
Operate Delay Time |
||
RsDlTmms |
Reset Delay Time |
LN: Undervoltage Name: PTUV |
Ln Class: |
PTUV |
Undervoltage |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate |
||
TmVSt |
Active curve characteristic |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
TmVCrv |
Operating Curve Type |
||
TmVChr33 |
Multiline curve characteristic definition |
||
StrVal |
Start Value |
||
TmMult |
Time Dial Multiplier |
||
MinOpTmms |
Minimum Operate Time |
||
MaxOpTmms |
Maximum Operate Time |
||
OpDlTmms |
Operate Delay Time |
||
RsDlTmms |
Reset Delay Time |
LN: Underpower factor Name: PUPF |
Ln Class: |
PUPF |
Underpower factor |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate |
||
BlkA |
Blocked below minimum operating current |
||
BlkV |
Blocked below minimum operating voltage |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
StrVal |
Start Value |
||
OpDlTmms |
Operate Delay Time |
||
RsDlTmms |
Reset Delay Time |
||
BlkValA |
Block Value (Minimum operating current) |
||
BlkValV |
Block Value (Minimum operating voltage) |
LN: Voltage controlled time overcurrent Name: PVOC |
Ln Class: |
PVOC |
Voltage controlled time overcurrent |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate |
||
AVSt |
Active curve characteristic |
||
TmASt |
Active curve characteristic |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
AVCrv |
Operating Curve Type (for voltage controlled current curve) |
||
AVChr33 |
Multiline curve characteristic definition |
||
TmACrv |
Operating Curve Type (for current) |
||
TmAChr33 |
Multiline curve characteristic definition |
||
TmMult |
Time Dial Multiplier |
||
MinOpTmms |
Minimum Operate Time |
||
MaxOpTmms |
Maximum Operate Time |
||
OpDlTmms |
Operate Delay Time |
||
TypRsCrv |
Type of Reset Curve |
||
RsDlTmms |
Reset Delay Time |
LN: Volts per Hz Name: PVPH |
Ln Class: |
PVPH |
Volts per Hz |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate |
||
VHzSt |
Active curve characteristic |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
VHzCrv |
Operating Curve Type |
||
VHzChr33 |
Multiline curve characteristic definition |
||
StrVal |
Volts per hertz Start Value |
||
OpDlTmms |
Operate Delay Time |
||
TypRsCrv |
Type of Reset Curve |
||
RsDlTmms |
Reset Delay Time |
||
TmMult |
Time Dial Multiplier |
||
MinOpTmms |
Minimum Operate Time |
||
MaxOpTmms |
Maximum Operate Time |
LN: Zero speed or underspeed Name: PZSU |
Ln Class: |
PZSU |
Zero speed or underspeed |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start |
||
Op |
Operate |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
StrVal |
Start Value (Speed) |
||
OpDlTmms |
Operate Delay Time |
||
RsDlTmms |
Reset Delay Time |
LN: Frequency Variation Name: QFVR |
Ln Class: |
QFVR |
Frequency Variation |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Controls |
|||
OpCntRs |
Resetable counter operation |
||
Status Information |
|||
Str |
Start (Frequency Variation Event in progress) |
||
UnHzStr |
Start (Underfrequency Variation Event in progress) |
||
OvHzStr |
Start (Overfrequency Variation Event in progress) |
||
Op |
Operate (Event finished but not Reset) |
||
Measured Values |
|||
HzVaTmms |
Frequency Variation Duration of the last completed event |
||
HzVa |
Frequency Variation Magnitude of the last completed event |
||
EvtCnt |
Event counter histogram |
||
Settings |
|||
UnHzStrVal |
Underfrequency Set Point |
||
OvHzStrVal |
Overfrequency Set Point |
LN: Current Transient Name: QITR |
Ln Class: |
QITR |
Current Transient |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Controls |
|||
OpCntRs |
Resetable counter operation |
||
Status Information |
|||
Str |
Star |
||
Op |
Operate |
||
Measured Values |
|||
ATrsTmms |
Transient Duration |
||
MaxATrs |
Maxmum Current Transient Value |
||
EvtCnt |
Event counter histogram |
||
Settings |
|||
StrVal |
Current Transient Start Value |
LN: Current Unbalance Variation Name: QIUB |
Ln Class: |
QIUB |
Current Unbalance Variation |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Controls |
|||
OpCntRs |
Resetable counter operation |
||
Status Information |
|||
Str |
Star |
||
Op |
Operate |
||
Measured Values |
|||
AVaTmms |
Current Unbalance Variation Duration |
||
MaxAVa |
Maxmum Unbalance Deviation Value |
||
EvtCnt |
Event counter histogram |
||
Settings |
|||
UnbDetMth |
Unbalance Detection Method |
||
StrVal |
Current Unbalance Start Value |
LN: Voltage Transient Name: QVTR |
Ln Class: |
QVTR |
Voltage Transient |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Controls |
|||
OpCntRs |
Resetable counter operation |
||
Status Information |
|||
Str |
Star |
||
Op |
Operate |
||
Measured Values |
|||
VTrsTmms |
Transient Duration |
||
MaxVTrs |
Maxmum Voltage Transient Value |
||
EvtCnt |
Event counter histogram |
||
Settings |
|||
StrVal |
Voltage Transient Start Value |
LN: Voltage Unbalance Variation Name: QVUB |
Ln Class: |
QVUB |
Voltage Unbalance Variation |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Controls |
|||
OpCntRs |
Resetable counter operation |
||
Str |
Star |
||
Op |
Operate |
||
Status Information |
|||
Measured Values |
|||
VVaTmms |
Voltage Unbalance Variation Duration |
||
MaxAVa |
Maxmum Unbalance Deviation Value |
||
EvtCnt |
Event counter histogram |
||
Settings |
|||
UnbDetMth |
Unbalance Detection Method |
||
StrVal |
Voltage Unbalance Start Value |
LN: Voltage Variation Name: QVVR |
Ln Class: |
QVVR |
Voltage Variation |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Controls |
|||
OpCntRs |
Resetable counter operation |
||
Status Information |
|||
Str |
Start (Voltage Variation Event in progress) |
||
DipStr |
Start (Voltage Dip Event in progress) |
||
SwlStr |
Start (Voltage Swell Event in progress) |
||
Op |
Operate (Event finished but not Reset) |
||
VVaTmms |
Voltage Variation Duration of the last completed event |
||
Measured Values |
|||
VVa |
Voltage Variation Magnitude of the last completed event |
||
EvtCnt |
Event counter histogram |
||
Settings |
|||
PQStd |
Power Quality Standard (Enumerated –UNIPEDE, NRS048, CIGRE C4.07, EPRI, IEEE,Custom) |
||
DipStrVal |
Voltage Dip Set Point |
||
SwlStrVal |
Voltage Swell Set Point |
||
IntStrVal |
Voltage Interruption Set Point |
||
IntDetMth |
Interruption Detection Method |
LN: Disturbance recorder channel analogue Name: RADR |
Ln Class: |
RADR |
Disturbance recorder channel analogue |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
ChTrg |
Channel triggered |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
ChNum1 |
Channel number |
||
TrgMod |
Trigger mode (internal trigger, external or both) |
||
LevMod |
Level Trigger Mode |
||
HiTrgLev |
High (positive) trigger level |
||
LoTrgLev |
Low (negative) trigger level |
||
PreTmms |
Pre-trigger time |
||
PstTmms |
Post-trigger time |
LN: Disturbance recorder channel binary Name: RBDR |
Ln Class: |
RBDR |
Disturbance recorder channel binary |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
ChTrg |
Channel triggered |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
ChNum |
Channel number |
||
TrgMod |
Trigger mode (internal trigger, external or both) |
||
LevMod |
Level Trigger Mode |
||
PreTmms |
Pre-trigger time |
||
PstTmms |
Post-trigger time |
LN: Breaker failure Name: RBRF |
Ln Class: |
RBRF |
Breaker failure |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start, timer running |
||
OpEx |
Breaker failure trip (“external trip”) |
||
OpIn |
Operate, retrip (“internal trip”) |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
FailMod |
Breaker Failure Detection Mode (current, breaker status, both, other) |
||
FailTmms |
Breaker Failure Time Delay for bus bar trip |
||
SPlTrTmms |
Single Pole Retrip Time Delay |
||
TPTrTmms |
Three Pole Retrip Time Delay |
||
DetValA |
Current Detector Value |
||
ReTrMod |
Retrip Mode |
LN: Directional element Name: RDIR |
Ln Class: |
RDIR |
Directional element |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Dir |
Direction |
||
Settings |
|||
ChrAng |
Characteristic Angle |
||
MinFwdAng |
Minimum Phase Angle in Forward Direction |
||
MinRvAng |
Minimum Phase Angle in Reverse Direction |
||
MaxFwdAng |
Maximum Phase Angle in Forward Direction |
||
MaxRvAng |
Maximum Phase Angle in Reverse Direction |
||
BlkValA |
Minimum operating current |
||
BlkValV |
Minimum operating voltage |
||
PolQty |
Polarising Quantity |
||
MinPPV |
Min Phase-Phase Voltage |
LN: Disturbance recorder function Name: RDRE |
Ln Class: |
RDRE |
Disturbance recorder function |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Controls |
|||
RcdTrg |
Trigger recorder |
||
MemRs |
Reset recorder memory (set the pointer of memory start to the beginning) |
||
MemClr |
Clear Memory (erase all content of the memory) |
||
OpCntRs |
Resetable operation counter |
||
Status Information |
|||
RcdMade |
Recording made |
||
FltNum |
Fault Number |
||
GriFltNum |
Grid Fault Number |
||
RcdStr |
Recording started |
||
MemUsed |
Memory used in % |
||
Settings |
|||
TrgMod |
Trigger mode (internal trigger, external or both) |
||
LevMod |
Level Trigger Mode |
||
PreTmms |
Pre-trigger time |
||
PstTmms |
Post-trigger time |
||
MemFull |
Memory full level |
||
MaxNumRcd |
Maximum number of records |
||
ReTrgMod |
Retrigger Mode |
||
PerTrgTms |
Periodic trigger time in s |
||
ExclTmms |
Exclusion time |
||
OpMod |
Operation mode (Saturation, Overwrite) |
||
StoRte |
Storage rate, i.e. sampling rate of the disturbance recorder |
LN: Disturbance record handling Name: RDRS |
Ln Class: |
RDRS |
Disturbance record handling |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Controls |
|||
AutoUpLod |
Automatic upload |
||
DltRcd |
Delete record |
LN: Fault locator Name: RFLO |
Ln Class: |
RFLO |
Fault locator |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Measured Values |
|||
FltZ |
Fault Impedance |
||
FltDiskm |
Fault Distance |
||
Status Information |
|||
FltLoop |
Fault Loop |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
LN: Power swing detection/blocking Name: RPSB |
Ln Class: |
RPSB |
Power swing detection/blocking |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Str |
Start (Power Swing Detected) |
||
Op |
Operate (Out of step Tripping) |
||
BlkZn |
Blocking of correlated PDIS zone |
||
Controls |
|||
OpCntRs |
Resetable operation counter |
||
Settings |
|||
ZeroEna |
Zero Enable |
||
NgEna |
Negative Sequence Current Supervision Enabled |
||
MaxEna |
Max Current Supervision Enabled |
||
SwgVal |
Power Swing Delta |
||
SwgRis |
Power Swing Delta R |
||
SwgReact |
Power Swing Delta X |
||
SwgTmms |
Power Swing Time |
||
UnBlkTmms |
Unblocking Time |
||
MaxNumSlp |
Maximum number of pole slips until tripping (Op, Out of step tripping) |
||
EvTmms |
Evaluation time (time window, Out of step tripping) |
LN: Autoreclosing Name: RREC |
Ln Class: |
RREC |
Autoreclosing |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Controls |
|||
Mod |
Mode |
||
Status Information |
|||
Blk |
Dynamical blocking of autoreclosure |
||
BlkRef |
Blocking reference shows the sender of the blocking singnal |
||
TrBeh |
Defines Single or Three Pole Tripping (mostly resulting from combination TrMod and RecCyc) for the next trip to be subscribed by the Protection. |
||
RecCyc |
Actual Reclose Cycle (number between 1 and UseCyc) |
||
OpCls |
Operation “close switch” issued to close the XCBR |
||
AutoRecSt |
Auto Reclosing Status |
||
AutoCycSt |
Auto Reclosing Cycle Status |
||
Settings |
|||
TrMod1 |
Indicates if Single Pole Tripping allowed or Three Pole Tripping always requested in the cycle indicated by the DO index |
||
MaxCyc |
Maximum number of Reclose cycles |
||
UseCyc |
Used actual set maximum number of Reclose cycles |
||
MaxTmms |
Maximum time after fault detection during which autoreclosing is permitted |
||
RecTmms1 |
Reclose Time i.e. time to reclose command after trip in the cycle inidicated by the DO index |
||
PlsTmms |
Close Pulse Time |
||
ClsTmms |
Time the breaker has to stay closed for successful autoreclosing |
||
RclTmms |
Reclaim Time |
LN: Switch-on-to-fault function Name: RSOF |
Ln Class: |
RSOF |
Switch-on-to-fault function |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
SwFltSt |
Switch-on-to-fault state |
||
PosOpn |
Breaker has been openend by command (to be subscribed by XCBR) |
||
PosCls |
Breaker has been closed e.g. by command (to be subscribed by XCBR) |
||
TrFltSt |
Trip Fault State: TRUE = Trip by start, FALSE = Trip by Operate (send e.g. to PTRC) |
||
BlkFltSt |
Block Fault State: TRUE = Blocked by Switch-on-to-fault condition, FALSE =Not blocked by Normal condition (send e.g. to RREC) |
||
Settings |
|||
MinTmms |
Minimum time before transition form normal to switch-on-to-fault state |
||
MaxTmms |
Maximum time after fault detection during which autoreclosing is permitted |
LN: Synchronism-check Name: RSYN |
Ln Class: |
RSYN |
Synchronism-check |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Status Information |
|||
Rel |
Release |
||
VInd |
Voltage Difference Indicator |
||
AngInd |
Angle Difference Indicator |
||
HzInd |
Frequency Difference Indicator |
||
SynPrg |
Synchrocheck in progress |
||
Measured Values |
|||
DifVClc |
Calculated Difference in Voltage |
||
DifHzClc |
Calculated Difference in Frequency |
||
DifAngClc |
Calculated Difference of Phase Angle |
||
Settings |
|||
DifV |
Difference Voltage |
||
DifHz |
Difference Frequency |
||
DifAng |
Difference Phase Angle |
||
LivDeaMod |
Live Dead Mode |
||
DeaLinVal |
Dead Line Value |
||
LivLinVal |
Live Line Value |
||
DeaBusVal |
Dead Bus Value |
||
LivBusVal |
Live Bus Value |
||
PlsTmms |
Close Pulse Time |
||
CBTmms |
Closing time of breaker |
LN: Teleprotection communication interfaces Name: RTPC |
Ln Class: |
RTPC |
Teleprotection communication interfaces |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Measured Values |
|||
BerCh |
Bit Error Rate of the communication channel. Used in case of a digital communication channel |
||
FerCh |
Frame Error Rate of the communication channel. Used in case of a digital communication channel. May be vendor specific |
||
LoopTestTm |
Time measured at last loop test |
||
CarrierLevel |
Power of received signal in case of an analogue communication channel |
||
SNR |
Signal to noise ratio in dB, used in case of analogue communication |
||
Status Information |
|||
EEHealth |
Communication channel health |
||
GrdRxCmdRx |
Alarm situation: Guard received together with the command, may indicate interference on the channel. Used in case of an analogue communication channel |
||
LosOfSignal |
Alarm situation: No signal received, indicates a channel problem |
||
TxCmdCnt1 |
For diagnostics: Transmitted commands counters (for each command) |
||
RxCmdCnt1 |
For diagnostics: Received commands counters (for each command) |
||
LosOfSyn |
Alarm situation: Loss of synchronism. Indicates that there is no synchronization between the transmitter and the receiver, i.e., no communication is possible. Used in case of a digital communication channel |
||
Settings |
|||
NumTxCmd |
Number of used binary transmit commands. |
||
NumRxCmd |
Number of used binary receive commands. |
||
TpcTxMod1 |
Teleprotection application mode in Transmit direction for each command (Unused, Blocking, Permissive, Direct, Unblocking, Status) |
||
TpcRxMod1 |
Teleprotection application mode in Receive direction for each command ((Unused, Blocking, Permissive, Direct, Unblocking, Status) |
||
SecTmms |
Pickup security timer on loss of carrier guard signal: if a command is received within SecTmms after the guard has disappeared this command is considered valid, used in case of an analogue communication channel |
||
BoostRatiodB |
Level of increased power during the transmission of a command in dB. Used in case of an analogue communication channel |
||
TxPwrPEPdBm |
Transmit power (peak envelope power) in dBm. Used in case of an analogue communication channel |
||
TxCtrHz |
Transmit center frequency. Used in case of an analogue communication channel |
||
RxCtrHz |
Receive center frequency. Used in case of an analogue communication channel |
||
TxBwHz |
Transmit bandwidth. Used in case of an analogue communication channel |
||
RxBwHz |
Receive bandwidth. Used in case of an analogue communication channel |
LN: Monitoring and diagnostics for arcs Name: SARC |
Ln Class: |
SARC |
Monitoring and diagnostics for arcs |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpCntRs |
Resetable Operation Counter (Switch and fault arcs) |
||
Status Information |
|||
FACntRs |
Fault arc counter |
||
FADet |
Fault arc detected |
||
ArcCntRs |
Switch arc counter |
||
SwArcDet |
Switch arc detected |
LN: Circuit breaker wear supervision Name: SCBR |
Ln Class: |
SCBR |
Circuit breaker wear supervision |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpCntRs |
Resetable Operation Counter |
||
Status Information |
|||
Col1Opn |
Open command of trip coil 1 |
||
Col2Opn |
Open command of trip coil 2 (usually as backup protection coil) |
||
AbrAlm |
Contact abrasion alarm |
||
AbrWrn |
Contact abrasion warning |
||
Measured Values |
|||
AccAbr |
Cumulated abrasion coefficients |
||
TripA |
Current that was interrupted during last open operation |
||
ActAbrCoef |
Abrasion coefficient of last open operation |
||
Settings |
|||
AbrAlmLev |
Abrasion coefficient sum threshold for alarm state |
||
AbrWrnLev |
Abrasion coefficient sum threshold for warning state |
LN: Insulation medium supervision (gas) Name: SIMG |
Ln Class: |
SIMG |
Insulation medium supervision (gas) |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
Pres |
Insulation gas pressure |
||
Den |
Insulation gas density |
||
Tmp |
Insulation gas temperature |
||
CngIntv |
Trend of insulation medium, expressed as time to blocking level |
||
Status Information |
|||
InsAlm |
Insulation gas critical (refill isolation medium) |
||
InsBlk |
Insulation gas not safe (block device operation) |
||
InsTr |
Insulation gas dangerous (trip for device isolation) |
||
PresAlm |
Insulation gas pressure alarm |
||
DenAlm |
Insulation gas density alarm |
||
TmpAlm |
Insulation gas temperature alarm |
||
InsLevMax |
Insulation gas level maximum (relates to predefined filling value) |
||
InsLevMin |
Insulation gas level minimum (relates to predefined filling value) |
LN: Insulation medium supervision (liquid) Name: SIML |
Ln Class: |
SIML |
Insulation medium supervision (liquid) |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
Tmp |
Insulation liquid temperature |
||
Lev |
Insulation liquid level |
||
Pres |
Insulation liquid pressure |
||
H2O |
Relative saturation of moisture in insulating liquid (in %) |
||
H2OPap |
Relative saturation of moisture in insulating paper (in %) |
||
H2OAir |
Relative saturation of moisture in air in expansion volume (in %) |
||
H2OTmp |
Temperature of insulating liquid at point of H2O measurement |
||
H2ppm |
Measurement of Hydrogen (H2 in ppm) |
||
N2ppm |
Measurement of N2 in ppm |
||
COppm |
Measurement of CO in ppm |
||
CO2ppm |
Measurement of CO2 in ppm |
||
CH4ppm |
Measurement of CH4 in ppm |
||
C2H2ppm |
Measurement of C2H2 in ppm |
||
C2H4ppm |
Measurement of C2H4 in ppm |
||
C2H6ppm |
Measurement of C2H6 in ppm |
||
O2ppm |
Measurement of O2 in ppm |
||
TDCG |
Measurement of total dissolved combustable gases (TDCG) |
||
FltGas |
Fault gas volume in Buchholz relay |
||
Status Information |
|||
InsAlm |
Insulation liquid critical (refill insulation medium) |
||
InsBlk |
Insulation liquid not safe (block device operation) |
||
InsTr |
Insulation liquid dangerous (trip for device isolation) |
||
TmpAlm |
Insulation liquid temperature alarm |
||
GasInsAlm |
Gas in insulation liquid alarm (may be used for Buchholz alarm) |
||
GasInsTr |
Gas in insulation liquid trip (may be used for Buchholz trip) |
||
GasFlwTr |
Insulation liquid flow trip because of gas (may be used for Buchholz trip) |
||
InsLevMax |
Insulation liquid level maximum |
||
InsLevMin |
Insulation liquid level minimum |
||
H2Alm |
H2 alarm |
||
MstAlm |
Moisture sensor alarm |
LN: Tap changer Supervision Name: SLTC |
Ln Class: |
SLTC |
Tap changer Supervision |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
Torq |
Drive torque |
||
MotDrvA |
Motor drive current |
||
AbrPrt |
Abrasion (in %) of parts subject to wear |
||
Status Information |
|||
OilFil |
Oil filtration running |
||
MotDrvBlk |
Motor drive overcurrent blocking |
||
VacCelAlm |
Circuit status of vacuum cell (ANSI) |
||
OilFilTr |
Oil filter unit trip |
LN: Supervision of Operating Mechanism Name: SOPM |
Ln Class: |
SOPM |
Supervision of Operating Mechanism |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Metered Values |
|||
En |
Stored energy (eg. stored energy or remaining energy) |
||
HyPres |
Hydraulic pressure |
||
HyTmp |
Hydraulic temperature |
||
MotTm |
Operating time of the motor |
||
MotA |
Motor current |
||
Tmp |
Temperature inside the drive cubicle |
||
ChaIntv |
Time interval between last two charging operations |
||
MotStr |
Number of motor starts |
||
Status Information |
|||
MotOp |
Indicates if the motor is running |
||
MotStrAlm |
Alarm for number of motor starts exceeds MotAlmNum |
||
HyAlm |
Hydraulic Alarm |
||
HyBlk |
Block of operation due to hydraulic |
||
EnBlk |
Energy block |
||
EnAlm |
Energy alarm |
||
MotAlm |
Motor operating time exceeded |
||
HeatAlm |
Heater alarm |
||
Settings |
|||
MotAlmTms |
Alarm level for motor run time in s |
||
MotAlmNum |
Alarm level for number of pump starts |
||
MotStrIntv |
Time interval for motor starts reset |
LN: Monitoring and diagnostics for partial discharges Name: SPDC |
Ln Class: |
SPDC |
Monitoring and diagnostics for partial discharges |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpCnt |
Operation counter |
||
Measured Values |
|||
AcuPaDsch |
Acoustic level of partial discharge |
||
AppPaDsch |
Apparent charge of partial discharge, peak level (PD) |
||
NQS |
Average dischcarge current |
||
UHFPaDsch |
UHF level of partial discharge |
||
Status Information |
|||
PaDschAlm |
Partial discharge alarm |
||
Settings |
|||
CtrHz |
Center Frequency of measurement unit according to IEC 60270, clause 3.8 |
||
Bndwid |
Bandwidth of measurement unit according to IEC 60270, clause 3.8 |
LN: Power Transformer Supervision Name: SPTR |
Ln Class: |
SPTR |
Power Transformer Supervision |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
AgeRat |
Aging rate |
||
BotTmp |
Bottom oil temperature |
||
CoreTmp |
Core temperature |
||
HPTmpClc |
Calculated winding hotspot temperature |
||
Status Information |
|||
HPTmpAlm |
Winding hotspot temperature alarm |
||
HPTmpOp |
Winding hotspot temperature operate |
||
HPTmpTr |
Winding hotspot temperature trip |
||
MbrAlm |
Leakage supervision alarm of tank conservator membrane |
||
CGAlm |
Core ground alarm |
LN: Circuit Switch Supervision Name: SSWI |
Ln Class: |
SSWI |
Circuit Switch Supervision |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
AbrPrt |
Abraison (in %) of parts subject to wear. |
||
AuxSwTmOpn |
Auxiliary switches timing Open |
||
AuxSwTmCls |
Auxiliary switches timing Close |
||
RctTmOpn |
Reaction time measurement Open |
||
RctTmCls |
Reaction time measurement |
||
OpSpdOpn |
Operation speed Open |
||
OpSpdCls |
Operation speed Close |
||
OpTmOpn |
Operation time Open |
||
OpTmCls |
Operation time Close |
||
Stk |
Contact Stroke |
||
OvStkOpn |
Overstroke Open |
||
OvStkCls |
Overstroke Close |
||
ColA |
Coil current |
||
Tmp |
Temperature e.g. inside drive mechanism |
||
Status Information |
|||
MechAlm |
Mechanical behavior alarm |
||
OpTmAlm |
Switch operating time exceeded |
||
ColAlm |
Coil alarm |
||
PhDif |
Phase discrepancy |
||
OpCnt |
Operation counter (not resettable) |
||
OpCntAlm |
Number of operations has exceeded the alarm level for number of operations |
||
OpCntWrn |
Number of operations exceeds the warning limit |
||
OpTmAlm |
Alarm when operation time reaches the alarm level |
||
OpTmWrn |
Warning when operation time reaches the warning level |
||
OpTmh |
Time since installation or last maintenance in hours |
||
Settings |
|||
OpAlmTmh |
Alarm level for operation time in hours |
||
OpWrnTmh |
Warning level for operation time in hours |
||
OpAlmNum |
Alarm level for number of operations |
||
OpWrnNum |
Warning level for number of operations |
LN: Temperature supervision Name: STMP |
Ln Class: |
STMP |
Temperature supervision |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
Tmp |
Temperaturen |
||
Status Information |
|||
Alm |
Temperature alarm level reached |
||
Trip |
Temperature trip level reached |
||
Settings |
|||
TmpAlmSpt |
Temperature alarm level set-point |
||
TmpTrSpt |
Temperature trip level set-point |
LN: Vibration supervision Name: SVBR |
Ln Class: |
SVBR |
Vibration supervision |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
Vbr |
Vibration level |
||
AxDsp |
Total axial displacement |
||
Status Information |
|||
Alm |
Vibration alarm level reached |
||
Trip |
Vibration trip level reached |
||
Settings |
|||
VbrAlmSpt |
Vibration alarm level set-point |
||
VbrTrSpt |
Vibration trip level set-point |
||
AxDspAlmSpt |
Axial displacement alarm level set-point |
||
AxDspTrpSpt |
Axial displacement trip level set-point |
LN: Angle Name: TANG |
Ln Class: |
TANG |
Angle |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
AngSv |
Angle |
||
Settings |
|||
SmpRte |
Sampling rate setting |
LN: Axial displacement Name: TAXD |
Ln Class: |
TAXD |
Axial displacement |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
AxDspSv |
Total axial displacement |
||
Settings |
|||
SmpIntv |
Sampling interval |
LN: Current transformer Name: TCTR |
Ln Class: |
TCTR |
Current transformer |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
||
Measured Values |
|||
AmpSv |
Current (Sampled value) |
||
Settings |
|||
ARtg |
Rated Current |
||
HzRtg |
Rated Frequency |
||
Rat |
Winding ratio of an external current transformer (transducer) if applicable |
||
Cor |
Current phasor magnitude correction of an external current transformer |
||
AngCor |
Current phasor angle correction of an external current transformer |
LN: Distance Name: TDST |
Ln Class: |
TDST |
Distance |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
DisSv |
Distance [m] |
||
Settings |
|||
SmpRte |
Sampling rate setting |
LN: Liquid flow Name: TFLW |
Ln Class: |
TFLW |
Liquid flow |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
FlwSv |
Liquid flow rate [m3/s] |
||
Settings |
|||
SmpRte |
Sampling rate setting |
LN: Frequency Name: TFRQ |
Ln Class: |
TFRQ |
Frequency |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
HzSv |
Frequency [Hz] related to non-electrical values |
||
Settings |
|||
SmpRte |
Sampling rate setting |
LN: Humidity Name: THUM |
Ln Class: |
THUM |
Humidity |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
HumSv |
Humidity [%] |
||
Settings |
|||
SmpRte |
Sampling rate setting |
LN: Media level Name: TLVL |
Ln Class: |
TLVL |
Media level |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
LevPctSv |
Level [%] |
||
Settings |
|||
SmpRte |
Sampling rate setting |
LN: Magnetic field Name: TMGF |
Ln Class: |
TMGF |
Magnetic field |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
MagFldSv |
Magnetic field strength / flux density (T) |
||
Settings |
|||
SmpRte |
Sampling rate setting |
LN: Movement sensor Name: TMVM |
Ln Class: |
TMVM |
Movement sensor |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
MvmRteSv |
Movement rate [m/s] |
||
Settings |
|||
SmpRte |
Sampling rate setting |
LN: Position indicator Name: TPOS |
Ln Class: |
TPOS |
Position indicator |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
PosPctSv |
Position given as percentage of full movement [%] |
||
Settings |
|||
SmpRte |
Sampling rate setting |
LN: Pressure sensor Name: TPRS |
Ln Class: |
TPRS |
Pressure sensor |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
PresSv |
Pressure of media [Pa] |
||
Settings |
|||
SmpRte |
Sampling rate setting |
LN: Rotation transmitter Name: TRTN |
Ln Class: |
TRTN |
Rotation transmitter |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
RotSpdSv |
Rotational speed [1/s] |
||
Settings |
|||
SmpRte |
Sampling rate setting |
LN: Sound pressure sensor Name: TSND |
Ln Class: |
TSND |
Sound pressure sensor |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
SndSv |
Sound pressure level [dB] |
||
Settings |
|||
SmpRte |
Sampling rate setting |
LN: Temperature sensor Name: TTMP |
Ln Class: |
TTMP |
Temperature sensor |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
TmpSv |
Temperature [°C] |
||
Settings |
|||
SmpRte |
Sampling rate setting |
LN: Mechanical tension / stress Name: TTNS |
Ln Class: |
TTNS |
Mechanical tension / stress |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
Tns |
Mechanical stress [N] |
||
Settings |
|||
SmpRte |
Sampling rate setting |
LN: Vibration sensor Name: TVBR |
Ln Class: |
TVBR |
Vibration sensor |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
VbrSv |
Vibration [mm/s2] |
||
Settings |
|||
SmpInt |
Sampling rate setting |
LN: Voltage transformer Name: TVTR |
Ln Class: |
TVTR |
Voltage transformer |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
||
Measured Values |
|||
VolSv |
Voltage (sampled value) |
||
Status Information |
|||
FuFail |
TVTR fuse failure |
||
Settings |
|||
VRtg |
Rated Voltage |
||
HzRtg |
Rated frequency |
||
Rat |
Winding ratio of external voltage transformer (transducer) if applicable |
||
Cor |
Voltage phasor magnitude correction of external voltage transformer |
||
AngCor |
Voltage phasor angle correction of external voltage transformer |
LN: Water acidity Name: TWPH |
Ln Class: |
TWPH |
Water acidity |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
Measured Values |
|||
H2OPhSv |
WaterpH level (0-14) |
||
Settings |
|||
SmpInt |
Sampling rate setting |
LN: Circuit breaker Name: XCBR |
Ln Class: |
XCBR |
Circuit breaker |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
LocKey |
Local or remote key (local means without substation automation communication, hardwired direct control) |
||
LocSta |
Remote Control Blocked |
||
Loc |
Local Control Behavior |
||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpCnt |
Operation counter |
||
Controls |
|||
Pos |
Switch position |
||
BlkOpn |
Block opening |
||
BlkCls |
Block closing |
||
ChaMotEna |
Charger motor enabled |
||
Metered Values |
|||
SumSwARs |
Sum of Switched Amperes, resetable |
||
Status Information |
|||
CBOpCap |
Circuit breaker operating capability |
||
POWCap |
Point On Wave switching capability |
||
MaxOpCap |
Circuit breaker operating capability when fully charged |
LN: Circuit switch Name: XSWI |
Ln Class: |
XSWI |
Circuit switch |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
LocKey |
Local or remote key |
||
LocSta |
Remote Control Blocked |
||
Loc |
Local Control Behavior |
||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpCnt |
Operation counter |
||
Controls |
|||
Pos |
Switch position |
||
BlkOpn |
Block opening |
||
BlkCls |
Block closing |
||
ChaMotEna |
Charger motor enabled |
||
Status Information |
|||
SwTyp |
Switch type |
||
SwOpCap |
Switch operating capability |
||
MaxOpCap |
Circuit switch operating capability when fully charged |
LN: Earth fault neutralizer (Petersen coil) Name: YEFN |
Ln Class: |
YEFN |
Earth fault neutralizer (Petersen coil) |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
LocKey |
Local-remote key |
||
LocSta |
Remote Control Blocked |
||
Loc |
Local Control Behavior |
||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
||
Measured Values |
|||
ECA |
Earth coil current |
||
Controls |
|||
ColTapPos |
Coil Tap Position |
||
ColPos |
Plunge Core Position |
LN: Tap changer Name: YLTC |
Ln Class: |
YLTC |
Tap changer |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
||
Controls |
|||
TapPos |
Change Tap Position to dedicated position |
||
TapChg |
Change Tap Position (stop, higher, lower) |
||
Status Information |
|||
EndPosR |
End position raise reached |
||
EndPosL |
End position lower reached |
||
OoStep |
Out of step alarm: supervision of diverter selector switch synchronism |
||
LTCCycAlm |
LTC switching cycle incomplete: tap change operation without diverter switch operation |
LN: Power shunt Name: YPSH |
Ln Class: |
YPSH |
Power shunt |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
||
Controls |
|||
Pos |
Switch position |
||
BlkOpn |
Block opening |
||
BlkCls |
Block closing |
||
ShOpCap |
Operating capability |
||
ChaMotEna |
Charger motor enabled |
||
MaxOpCap |
Power shunt operating capability when fully charged |
LN: Power transformer Name: YPTR |
Ln Class: |
YPTR |
Power transformer |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
||
Measured Values |
|||
LodFact |
Load factor (apparent power / rated power) |
||
MaxPwr |
Calculated maximum permissible permanent power (overload) [W] |
||
OvlTmm |
Calculated maximum permissible overload time with cooling unit [min] |
||
OvlTmmEmg |
Calculated maximum permissible overload time without cooling unit (emergency case) [min] |
||
Status Information |
|||
OANL |
Operation at no load |
||
OpOvA |
Operation at overcurrent |
||
OpOvV |
Operation at overvoltage |
||
OpUnV |
Operation at undervoltage |
||
Settings |
|||
HiVRtg |
Rated Voltage (High voltage level) |
||
LoVRtg |
Rated Voltage (Low voltage level) |
||
PwrRtg |
Rated power |
||
MaxPwrSet |
Maximum permissible permanent power (overload) [W] |
||
OvlTmmSet |
Maximum permissible overload time with cooling unit [min] |
||
OvlTmmEmgSet |
Maximum permissible overload time without cooling unit (emergency case) [min] |
LN: Auxiliary network Name: ZAXN |
Ln Class: |
ZAXN |
Auxiliary network |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
||
Measured Values |
|||
Vol |
Voltage of the auxiliary network |
||
Amp |
Current of the auxiliary network |
LN: Battery Name: ZBAT |
Ln Class: |
ZBAT |
Battery |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
||
Measured Values |
|||
Vol |
Battery voltage |
||
VolChgRte |
Rate of battery voltage change |
||
Amp |
Battery drain current |
||
Controls |
|||
BatTest |
Start battery test |
||
Status Information |
|||
TestRsl |
Battery Test Results |
||
BatHi |
Battery high (voltage or charge – Overcharge) |
||
BatLo |
Battery low (voltage or charge) |
||
Settings |
|||
LoBatVal |
Low battery alarm value |
||
HiBatVal |
High battery alarm value |
LN: Bushing Name: ZBSH |
Ln Class: |
ZBSH |
Bushing |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
||
Measured Values |
|||
React |
Relative capacitance of bushing related to the data object RefReact |
||
AbsReact |
Online capacitance, absolute value |
||
LosFact |
Loss Factor (tan delta) |
||
Vol |
Voltage of bushing measuring tap |
||
DisplA |
Displacement current: apparent current at measuring tap |
||
LeakA |
Leakage current: active current at measuring tap |
||
Settings |
|||
RefReact |
Reference capacitance for bushing at commissioning |
||
RefPF |
Reference power factor for bushing at commissioning |
||
RefV |
Reference voltage for bushing at commissioning |
LN: Power cable Name: ZCAB |
Ln Class: |
ZCAB |
Power cable |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
LN: Capacitor bank Name: ZCAP |
Ln Class: |
ZCAP |
Capacitor bank |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
||
Controls |
|||
CapDS |
Capacitor bank device status |
||
Status Information |
|||
DschBlk |
Blocked due to discharge |
LN: Converter Name: ZCON |
Ln Class: |
ZCON |
Converter |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
LN: Generator Name: ZGEN |
Ln Class: |
ZGEN |
Generator |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
||
Controls |
|||
GnCtl |
Generator control |
||
DExt |
De-excitation |
||
AuxSCO |
Aux. supply change over |
||
ReactPwrR |
Reactive power raise |
||
ReactPwrL |
Reactive power lower |
||
Measured Values |
|||
GnSpd |
Generator Speed |
||
Status Information |
|||
GnSt |
Generator state (stopped, Starting, Started, Stopping, Disabled) |
||
OANL |
Operation at no load |
||
ClkRot |
Phase rotation clockwise |
||
CntClkRot |
Phase rotation counter clockwise |
||
OpUnExt |
Operation at under-excitation |
||
OpOvExt |
Operation at over-excitation |
||
LosOil |
Loss of oil |
||
LosVac |
Loss of vacuum |
||
PresAlm |
Low pressure alarm |
||
Settings |
|||
DmdPwr |
Demanded power |
||
PwrRtg |
Rated power |
||
VRtg |
Rated Voltage |
LN: Gas insulated line Name: ZGIL |
Ln Class: |
ZGIL |
Gas insulated line |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
LN: Power overhead line Name: ZLIN |
Ln Class: |
ZLIN |
Power overhead line |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
||
Settings |
|||
LinLenkm |
Line length in km |
||
RPs |
Positive-sequence line resistance |
||
RZer |
Zero-sequence line resistance |
||
XZer |
Zero-sequence line reactance |
||
ZPsMag |
Positive-sequence line impedance value |
||
ZPsAng |
Positive-sequence line impedance angle |
||
ZZerMag |
Zero-sequence line impedance value |
||
ZZerAng |
Zero-sequence line impedance angle |
||
RmZer |
Mutual resistance |
||
XmZer |
Mutual reactance |
||
ZmZerMag |
Mutual impedance value |
||
ZmZerAng |
Mutual impedance angle |
LN: Motor Name: ZMOT |
Ln Class: |
ZMOT |
Motor |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
||
Controls |
|||
DExt |
De-excitation |
||
Status Information |
|||
LosOil |
Loss of oil |
||
LosVac |
Loss of vacuum |
||
PresAlm |
Low pressure alarm |
LN: Reactor Name: ZREA |
Ln Class: |
ZREA |
Reactor |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
LN: Neutral resistor Name: ZRES |
Ln Class: |
ZRES |
Neutral resistor |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
LN: Rotating reactive component Name: ZRRC |
Ln Class: |
ZRRC |
Rotating reactive component |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
LN: Surge arrestor Name: ZSAR |
Ln Class: |
ZSAR |
Surge arrestor |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
||
Status Information |
|||
OPSA |
Operation of surge arrestor |
LN: Semi-conductor controlled rectifier Name: ZSCR |
Ln Class: |
ZSCR |
Semi-conductor controlled rectifier |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
||
Status Information |
|||
Alm |
Control function alarm |
||
Settings |
|||
SetA |
Current setting (if operating to a fixed current) |
||
SetV |
Voltage setting (if operating to a fixed voltage) |
||
Controls |
|||
OpModRect |
Control mode setting (A, V, W) |
||
AmpSpt |
Current target set-point |
||
VolSpt |
Voltage target set-point |
LN: Synchronous machine Name: ZSMC |
Ln Class: |
ZSMC |
ynchronous machine |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
||
Status Information |
|||
RotDir |
Field rotation direction (TRUE = clockwise) |
||
Settings |
|||
PwrRtg |
Rated apparent power [VA] |
||
VRtg |
Rated voltage [V] |
||
ARtg |
Rated stator current [A] |
||
SpdRtg |
Synchronous machine rated speed [s-1] |
||
SpdCrit |
Synchronous machine critical speed of the generator [s-1] |
||
FldRisTmp |
Reference temperature for field resistance [°C] |
||
StatRisTmp |
Reference temperature for stator resistance [°C] |
||
StatRis |
Stator resistance [Ohm] |
||
PFRtg |
Rated power factor |
||
Iner |
Synchronous machine moment of inertia J [kgm2] |
||
FldAmpRtg |
Rated field current [A] |
||
FldAmpRtgO |
No-load field current for rated stator voltage [A] |
||
FldRis |
Field resistance [Ohm] |
||
BaseImp |
Base p.u. impedance [Ohm /phase] |
||
StatLReact |
Stator leakage reactance [p.u.] |
||
ReactXd |
D-axis synchronous reactance Xd [p.u.] (unsaturated) |
||
ReactXdPr |
D-axis transient synchronous reactance Xd’ [p.u.] (unsaturated) |
||
ReactXdSe |
D-axis Reactance Xd’’ [p.u.] (unsaturated) |
||
ReactXq |
Q-axis synchronous reactance Xq [p.u.] (unsaturated) |
||
ReactXqPr |
Q-axis transient reactance Xq’ [p.u.] (unsaturated) |
||
ReactXqSe |
Q-axis sub-transient reactance Xq’’ [p.u.] (unsaturated) |
||
ReactX0 |
Zero sequence Reactance X0 [p.u.] (unsaturated) |
||
ReactX2 |
Negative sequence Reactance X2 [p.u.] (unsaturated) |
||
TmCstTdP |
D-axis short circuit transient time constant Td’ [s] (unsaturated) |
||
TmCstTdS |
D-axis short-circuit sub-transient time constant Td’’[s] (unsaturated) |
||
TmCstTd0P |
D-axis open circuit transient time constant Td0’ [s] (unsaturated) |
||
TmCstTd0S |
D-axis open circuit sub-transient time constant Td0’’[s] (unsaturated) |
||
TmCstTqP |
Q-axis short circuit transient time constant Tq’ [s] (unsaturated) |
||
TmCstTqS |
Q-axis short circuit sub-transient time constant Tq ’’ [s] (unsaturated) |
||
TmCstTq0P |
Q-axis open circuit transient time constant Tq0’ [s] (unsaturated) |
||
TmCstTq0S |
Q-axis open circuit sub-transient time constant Tq0’’[s] (unsaturated) |
||
TmCstTa |
Armature time constant Ta[s] (unsaturated) |
||
SatCffS10 |
Saturation coefficient S1.0 |
||
SatCffS12 |
Saturation coefficient S1.2 |
LN: Thyristor controlled frequency converter Name: ZTCF |
Ln Class: |
ZTCF |
Thyristor controlled frequency converter |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
||
Settings |
|||
PwrHz |
Target frequency |
LN: Thyristor controlled reactive component Name: ZTCR |
Ln Class: |
ZTCR |
Thyristor controlled reactive component |
Sign |
Data Object Name |
Common Data Class |
Explanation |
Data Objects |
|||
Main Data Objects |
|||
EEHealth |
External equipment health |
||
EEName |
External equipment name plate |
||
OpTmh |
Operation time |
Lásd: |
|
|